Here we discuss the brief overview of different In-House testing methods carried out for RTD assemblies in the Calibration Laboratory. RTD Testing Methods The below list shows the different testing methods. 1. Calibration RTD calibration can be done as per IEC 751 / DIN 43760 Class A & B. Normally test is conducted for two points (i.e. 00 C & 1000 C), 3 point calibration or more can be followed. 2. Insulation Resistance Test at ambient (room temp.) at 500 VDC It should be more than 100 M ohms. 3. Insulation Resistance Test at 3200 C at 100 V DC IR should be more than 2 M ohms. More than 20 M ohms also can be offered. 4. N2 leakage test For the RTD sensor, after cap welding, the N2 leakage test should be carried out no leakage should be observed at 40 kg/cm2. 5. Response time test Response time test as per IEC 751 – (63.2% step change from ambient to 800C). For RTD without transmitter – 6 to 9 sec up to 6 mm OD of sheath. For RTD with thermowell – the response time will be ...
TILI Automation ,Thank you for coming! If you can’t see it, please use the search function!