Condensate Automation in the Sugar Industry

 In this article, we will study what condensate automation is? And what is the purpose of it?

The condensate automation systems are mainly employed in the sugar industry, distillery, paper industry, chemical industry, and so on.


The purpose of the condensate automation system is to cool down or reduce the temperature of the exhaust steam and the vapor outlet.

But in this article, we will discuss the condenser in the vacuum pan in the sugar industry.


Principle of Condenser Automation in Vacuum Pan

As the massecuite level in the pan rises, the rate of evaporation is reduced and therefore water required to create the vacuum is less.

When the vapor is mixed with injected water in the pan and the vacuum is created at the outlet tailpipe.

The temperature difference between vapor and vapor-condensate also affects vacuum generation.

The injection of water reduces the temperature as per Ambient.

Purpose of Condenser Automation

To control the water with respect to vacuum vapor and NCG load. Condenser automation reduces the water and steam requirement. And to facilitate the required vacuum generation using optimum water and power.


Jet Condenser Vessel and its Automation

To reduce the temperature of vapor the vapors from the pan body enter the jet condenser.

It is a multiple-entry condenser boxes.

 The condenser vessel is provided with multiple cold water entries with a set of spray nozzles and a spray jet.

The on/off valve for the respective nozzle is used to control the spray water quantity in the jet condenser in auto mode.

The strainer is provided to eliminate or remove the dust particles from the jet condenser vessel.

The diameter of the spray jet & nozzle is designed as per condenser capacity.

Here the spray water and jet nozzles are divided into 4 to 5 clusters.

The inlet water is connected to stainless steel strainer.

The temperature elements are installed to both the inlet and outlet of the jet condenser to sense the vapor temperature and send the signal to the controller through the temperature transmitter.

The pressure of spray water in the common header is maintained by controlling the injection pump through a variable frequency drive.

The inlet vapor temperature and tailpipe temperature were measured and controlled.

The condensate automation system employs the temperature loop control system to control the temperature.

Working on Condensate Automation System in the Batch Pan

In the sugar manufacturing process, the massecuite boiling in the batch pan under vacuum conditions is very dynamic.

The process begins with the concentration of massecuite in the boiling phase at a batch pan.


To generate vacuum the condenser is used in manual mode since massecuite boiling is a batch type process and manual condenser is used.


There is no scope of water flow during the entire process. These results in excess use of water and the manual mode condenser are designed for peak vapor.

The NCG load and air load through leakage for an extreme condition do not alter the quantity of injection water with respect to vapor load and NCG load.


Whereas this NCG load is higher at the start of boiling and negligible at end of boiling.


This result in higher volume and high power consumption even after the vapor and NCG load are decreased due to massecuite thickening.

To achieve the temperature difference of 10 Degrees to 12 Degrees Celsius all ON/OFF butterfly valves are controlled with an interlock timer which is an important parameter of the technical performance of the condenser this is achieved without disturbing the vacuum in the pan body.


If the vacuum drops by 5mmHg after the closure of any valve. The Switch ON signal will be sent immediately to the respective valve to maintain the vacuum setpoint of 635mmHg.


Now the respective valves will be closed by the Switch OFF signal issued by the controller from the pan floor.


The valve remains in the ON position in case of air failure. The condenser continuously uses the recycled water from the spray pond cooling system.


Temperature Control Loop System

Basically, the temperature loop control system includes a Temperature control valve, Temperature sensor (TS), Temperature Transmitter (TT), PID Controller, I/P Converter,


Temperature Gauge

A temperature Gauge is the temperature sensing device that detects the hotness or coolness of the fluid flowing through the line and the body.

This temperature gauge is only for displaying the temperature.


Temperature Sensor

A temperature sensor is a temperature sensing device that detects the hotness or coolness of the fluid flowing through the line and the body.


This sensor sends the signal to the controller in terms of electrical quantity. 


This system uses

Vapour temperature sensor

Inlet water temperature sensor

Tailpipe temperature sensor

Massecuite temperature sensor

Temperature Control valves

This unit reduces the temperature of the vacuum that consists of spray nozzles, through which cold water is sprayed to maintain the temperature difference of the vapor.


Positioner

A positioner in a control valve is a device that interfaces with the process controller that senses the exact position of the control valve.


The positioner sends the instrument air to the actuator so that the position of the valve stem changes according to the set point.


Controller

The controller receives electrical signals from all sensors installed at appropriate positions and sends appropriate signals to all the valves to maintain the temperature to desired set point.

Vacuum Transmitter

The vacuum transmitter (VT) senses the vacuum level and sends the signal to the controller for controlling the vacuum in the process.


The stainless steel strainer is provided at the water inlet to prevent the entry of dust particles into the condenser.

The temperature control valve regulates the quantity of the water to be sprayed.

The water inlet and outlet isolation valves are used to isolate the temperature control valve whenever maintenance of the control valve is to be carried out.

The bypass valve allows spray water flow to continue whenever the temperature control valve is under maintenance or becomes inoperable.

The cold water is sprayed at high velocity through spray nozzles and at an adequate quantity to reduce the temperature of vapor to the required temperature.

The temperature elements (TE) sense the temperature of the system installed in various locations and give a proportional current signal to the PID controller.

The PID controller then compares the process variable (Measured Value) received from the temperature sensors with a given setpoint (SP), generates an error signal, and is then given to the positioner, which determines the position of the temperature control valve to maintain the temperature difference.

This valve opens accordingly and sprays atomized water through the spray nozzle until the steam temperature reaches the set value, and re-closes to prevent the further spray of water after normal conditions have been restored,

i.e. Process Variable (PV) must be equal to SetPoint (SP). PV=SP

Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...