Skip to main content

Sox Nox Analyzer

 CEMS (Continuous Emissions Monitoring System) is required in power plants, cement plants, fertilizers, steel plants, etc., to monitor air pollution. CEMS measuring methods can be classified into two categories.


The data of Sox & Nox can be continuously sent to the pollution control board through a wireless network for monitoring purposes and optionally from the pollution board can do zero and span gas calibration through remote mode.


Extraction type

In-situ type

In this article, we discuss extraction type.


In analyzer panel, SS tubing material is used to avoid corrosion because of gas.


Sox Nox Analyzer

Sox Nox analyzer unit consists of suction pump, electric heater, No2 converter, rotameter, calibration gas cylinders, auto drain valve, SMPS, moisture detector, PLC unit, HMI.


Suction Pump

A suction pump is used to grab the sample from the chimney and sends it to the Sox Nox analyzer unit. It is provided with a 230 VAC power supply.


Electric Heater

In order to prevent the sample from moisture content, electric heat tracing is given on the upper side of the sample line.


SMPS

SMPS stands for Switch Mode Power Supply.


It is used to convert 230 V C to 24 VDC for PLC power source.


Moisture Detector

It is used to detect the moisture present in the sample line. If moisture detects the suction pump will be turned off.


An indicator is used to adjust the sensitivity of the moisture detector.


Two wire moisture transmitter can also be used instead of a detector.


Rotameter

Rotameter is used to control the flow of samples entering into the analyzer unit.


PLC

Digital inputs and outputs can be used to control analyzer functions and external components.


PLC is used to monitor heater temperature relay, moisture detector, and suction pump on/off.


No2 Converter

In the chimney, the sample contains “No content” which is difficult to measure so it is converted to No2.


Front Panel

It consists of an LCD display and a membrane keyboard. It is used to view the current data of sox and Nox values and able to edit calibration reference gas data.


We need to enter the span gas concentration in to the analyzer for calibration purpose.


Calibration Gas Cylinder

Zero and span gas cylinders installed and connected to the analyzer.


Span gas reference will vary for sox and NOx analyzers.


A total of 3 solenoid valves are used to control the flow of zero and span gases. These will be energized when the command is given from the local panel or through remote if provided.


Zero Gas

Sox Span Gas

Nox Span Gas

The Value of the Span Gas Cylinder should be around/more-than 80% of the measuring Range of the Analyzer.


The pressure regulator is installed on the zero and span gas cylinders to control the flow of calibration gas.


Sample Cooler

Sample cooler is used to cool down the sample temperature at required value.


Auto Drain Valve

Auto drain valve is used to drain the condensed liquid from the sample cell to a safe area.


Filter

Filter is used to collect dust particles in the sample line.


Analyzer Working Principle

The IR or UV sources will be used in the analyzer. It passes the IR or UV rays through a sample cell.


A Pyroelectric detector is used to measure the concentration of these IR or UV rays and the output of the detector is equivalent to the measured Sox or Nox.


Other than non-dispersive UV or IR, So2 can also be measured by UV fluorescence, Enhanced Laser, Fourier Transform Infra-red, gas chromatography, mass spectrometry.


Manual and automatic calibration can be performed in the sox-Nox analyzer.

Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution : A

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Electroma

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. ClO2