 Design the ladder logic for controlling the running state of the single phase motor by pressing START and STOP pushbuttons i.e. motor should remain in ON state after START pushbutton is pressed and should OFF when STOP pushbutton is pressed. We also have to check if the motor is running normally by pressing TEST pushbutton?

  • I0.0 – START pushbutton to Start Motor
  • I0.1 – STOP pushbutton to Stop Motor
  • I0.2 – Error signal from Motor to PLC.
  • Q0.0 –Single phase Motor

PLC Motor Logic

Press START button and I0.0 is ON. The Motor will keep running if no error occurred (I0.3 is OFF). The action can be practiced by a latching circuit which takes output Q0.0 as one of the input condition to keep the motor running even if the START button is not pressed (See normally open contact Q0.0 below I0.0).

When STOP button is pressed, I0.1 is ON and Q0.0 is OFF. The motor will stop running. If any error is occurred (I0.3 is ON), Y1 will be OFF and the motor will stop running.

When TEST is pressed (I0.2 is ON), Q0.0 is ON. The motor will start running if no error occurred (I0.3 is OFF). On the contrary, when TEST is released, the motor will stop running. The testing function is performed by this process.

Problem :
Here in the above logic, once motor started with TEST push button, we have to use STOP push button for stopping the motor. Because once motor started, the Latch  (Q 0.0) will activate and keep the motor running even after release of TEST push button

Case 2 : TEST Push button NC contact in series with LATCH
The above problem can be solved when we use NC contact of TEST push button in series with LATCH (Q 0.0) as shown in below figure. When we run the motor using TEST push button, the LATCH will not activate because the NC contact of TEST push button becomes NO.

 In real time applications, we may use Time Delays, One Shot Rise Pulse Inputs, Set – Reset and other instructions within the logic to avoid problems.
NOTE : Sometimes we may consider STOP push button within the TEST logic of motor. This is an example of the plc motor logic.

-END-


Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...