Design a ladder logic for providing lubricant for the gear box before the lathe spindle starts to run which aims to ensure that the lube oil pump motor starts first and the main motor starts subsequently ?
- I0.0– START pushbutton to Start Oil Pump Motor
- I0.1– START pushbutton to Stop Main Motor
- I0.2– STOP pushbutton to Stop Oil Pump Motor
- I0.3– STOP pushbutton to Stop Main Motor
- Q0.0– Oil Pump Motor
- Q0.1– Main Motor
This program is a typical application of the conditional control circuit. Q0.0 is ON when Oil Pump START button is pressed. Therefore, the oil pump will start to provide lubricant for the gear box of main motor (Q0.1).
Ladder Logic for Lube Oil Pump
Under the precondition of the operating state of the Oil pump, the main motor (Q0.1) will be ON when the Main motor START button is pressed. During the operation of main motor (Q0.1), oil pump (Q0.0) needs to provide lubricant continuously.
The oil pump will be stopped when Oil pump STOP button I0.2 is activated, and the main motor will be stopped when Main motor STOP button I0.3 is activated.
NOTE :
In real time applications, we may use Time Delays before starting main motor. After starting the Lube Oil Pump, there will be certain time delay ( say 30 sec, 2 min, 5 min) provided to make sure the lube oil pressure is sufficient before running main motor. In some cases time delays also provided during stopping the motors, based on specific applications.