Skip to main content

Tank Level Control in PLC

 Design a PLC program to control the liquid level in a tank. A level transmitter is used to measure the tank level into a standard current signal from 4 to 20mA as illustrated in the below process diagram.

Tank Level Control in PLC


PLC Program Logic
  1. The agitator motor is to be started and stopped by a pushbutton station.
  2. The solenoid valves are to be open (Energized) when the agitator is running.
  3. Pump N0.1 starts at the 75% liquid level and stops at the 25% level. The pump will run only if the agitator is running.
  4. On a high-level alarm (Tank 90%), an alarm light will come ON and stay on even if the tank level drops. An operator must press the reset button to turn off the light. On the high-level alarm, both the solenoid valve will also close (de-energize).
  5. A low-level alarm light shall be provided (Tank 10%), similar to the high level, and reset using the same pushbutton.
Scaling Tabular Column:


PLC Programming for Tank Level Control

PLC Program Description
Rung 0000:
Start/Stop PB latched with memory B3:0/0.

Rung 0001:
B3:0/0 enabled to turn on agitator (O: 0/0), Solenoid valve 1 (O:0/1) and Solenoid valve 2 (O:0/2).

Rung 0002:
Scaling block is used, Level transmitter gives output in mA (N7:0), to convert that into PLC range (N7:1), and scaling block is used.

Refer to the above tabular column for a respective range of values.

Rung 0003:
According to the program logic, we need to turn on the PUMP (O:0/3) at tank reaching 75%

And the pump still is in ON condition up to 25%, so comparator blocks are used to get this condition.

Agitator motor contact also connected in series as mentioned in program logic.

Rung 0004:
Memory coil connected to turn ON pump motor output.

Rung 0005 & 0006:
High-level alarm should turn ON when tank reaching 90% and should not turn off until alarm reset (I:0/2) is pressed.

Greater than or equal block is used to compare the real scaling value(N7:1) and register value.

Rung 0007 & 0008:
Low-level alarm should turn ON when tank reaching 10% and should not turn off until alarm reset (I:0/2) is pressed.

Less than or equal block is used to compare the real scaling value(N7:1) and register value.

Conclusion
We can use this example to understand the programming logic in Allen Bradley Programmable Logic Controller (PLC).

-END-

Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...