Skip to main content

Siemens S7-300 CPU Suffix Explanation

 Siemens S7-300 CPUs suffix explanation 

If you are in a new project and want to use Siemens S7-300 CPUs you are going to see a wide variety of CPUs under the name of CPU s7-300.

The first step is to open the SIMATIC manager software and choose a new project and go to Hardware configuration you will see the following table:

Siemens S7-300 CPU

In the previous table, there is a fixed pattern of CPU title
CPU XXXY-Z
Where

1. XXX is the number of CPU.

The greater the number the more capability the CPU is. Like the CPU scan cycle, memory size and number of IOs can be connected in the PLC.

2. Y is defining the type of CPU and it can be:

  • None: in this case the CPU is an ordinary modular PLC.
  • C: which stands for Compact, i.e. the CPU has a built in number of input output modules in addition to the modules that can be added to the CPU if we need to.
  • IFM: which stands for Integrated Function Module, it’s like the compact CPU but it has internal function module of high speed counters.
  • F: which stands for Fail Safe module, fail safe is a specific module that is used in cases where we need the maximum security of process controlling.
3. Z is defining the communication ports in the CPU and it can be:
  • None: In this case the CPU has only one port for MPI communication.
  • 2 or 2 DP: in this case the CPU ports are
1 MPI port and 1 DP port for Profibus communication.
C. 2 PTP: this CPU has 2 ports, first port for MPI and a second port for PTP (Point To Point) port

The PTP port can be used to communicate with printers and barcode readers.

D. 2PN/DP: This CPU has 2 ports first port for MPI or DP and 1 or 2 ports for Profinet connection.

E. 3PN/DP: This CPU had 1 port for MPI, 1 port for Profibus, and 1 or 2 ports for Profinet.
END 




Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...