Skip to main content

What is Displacer Level Sensor ?

 Displacer level sensor use Archimedes’ Principle to detect liquid level by continuously measuring the weight of a displacer rod immersed in the process liquid.

The displacer is cylindrical in shape with a constant cross-sectional area and made long or short as required. Standard heights range from 14 inches to 120 inches.

As liquid level increases, the displacer rod experiences a greater buoyant force, making it appear lighter to the sensing instrument, which interprets the loss of weight as an increase in level and transmits a proportional output signal.

As liquid level decreases, the buoyant force on the displacer rod decreases with a corresponding weight increase which is interpreted as decreasing level by the level sensor which then give a corresponding signal output.

Shown below is a typical displacer level sensor installation:




Although the basic theory of operation has been outlined above, in a practical displacer level sensor, the construction is engineered to achieve the desired measurement objective with sophisticated electronic circuitry.

In these types of displacer level sensors, the displacer is attached to a spring which restricts its movement for each increment of buoyancy (i.e. level change).

A transmitter incorporating a Linear Variable Differential Transformer (LVDT) is used to track the rise and fall of the displacer rod as liquid level changes. Sophisticated electronics is then used to process the voltage signal from the LDVT into a 4-20mA output signal.

Archimedes’ Principle Applied to the Displacer

According to Archimedes’ Principle, the buoyant force on an immersed object is always equal to the weight of the fluid volume displaced by the object.
Suppose in a displacer level sensor, we have a cylindrical displacer rod with density, ρ, radius, r, length, L, and process fluid of density, У. In this installation, the length of the displacer rod is proportional to the liquid level being measured:

Volume of displacer rod, V=πr2L

shown in the diagram for the displacer level sensor installation above, when the vessel is full, the displacer rod is completely immersed in the process fluid hence the volume of process fluid displaced is V=πr2L. When the level of the vessel is empty or minimum, volume of process fluid displaced is V = 0

Hence:

When vessel is full, buoyant force on displacer rod is given by:

Buoyant Force = weight of process fluid displaced

= πr2LУg (g = acceleration due to gravity)

Real weight of displacer = πr2Lρg

Net weight of displacer sensed by the LVDT, transmitter and associated electronics when vessel is full is:

= πr2Lρg−πr2LУg=πr2Lg(ρ–У)=Vg(ρ–У)

As can be seen above, the net weight sensed by the LVDT is proportional to the difference in density of the displacer rod (ρ) and that of the process fluid (У)

Therefore, the displacer rod must have a higher specific gravity than that of the liquid level being measured and have to be calibrated for the specific gravity of the liquid.

Typical specific gravity range for liquids where the displacer level sensor is applied is in the range of 0.25 to 1.5. Another point worth mentioning is that the range of the displacer level instrument is dependent only upon the length (L) of the displacer rod specified for the given application.

When vessel is empty or level is minimum,

Buoyant force on displacer = 0

Hence, weight sensed by the LVDT is =πr2Lρg

The LVDT registers a voltage signal at minimum vessel level and outputs a corresponding signal. The displacer length is determined by the operating range (span) specified, the specific gravity, pressure, and temperature of the process fluid. The diameter and weight are factory calculated to ensure correct operation and providing accurate 4-20mA output.

Areas of Application

The displacer level sensor is used in level measurement applications such as knock- out pots, condensate drums, separators, flash vessels, storage vessels and receiver tanks.


Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...