Ultrasonic Transmitters vs Guided Wave Radar for Level Measurement

 ULTRASONIC TECHNOLOGY

Ultrasonic is a non-contact level measurement method that uses sound waves to determine the process material being measured.

Ultrasonic transmitters operate by sending a sound wave, generated from a piezo electric transducer, to the media being measured. The device measures the length of time it takes for the reflected sound wave to return to the transducer.

A successful measurement depends on reflection from the process material in a straight line back to the transducer.

However, there are various influences that affect the return signal. Factors such as dust, heavy vapors, tank obstructions, surface turbulence, foam and even surface angles can affect the returning signal.

That is why the conditions that determine the characteristics of sound must be considered when using Ultrasonic measurement.

Other problematic aspects of Ultrasonic transmitters to consider include:

Vacuum Applications

Sound must travel through a medium (usually air)

The absence of air molecules prevents the propagation of sound waves

Surface Condition

Angles

Sound waves must be sent and received in a straight line

Reflective surfaces must be flat (i.e. Non-agitated/Non-turbulent condition)

Irregularities

Foam and other debris collected on the surface of the liquid which absorbs the sound waves and impedes their return sound travel to the sensor

Temperature Limits

Ultrasonic units are typically plastic with a maximum temperature of 140˚F (60˚C)

Varying process temperatures may generate inaccurate readings

Pressure Limits

Ultrasonic devices are not intended for extreme pressure limits

Maximum working pressures should not exceed of 30 PSIG (2 Bar)

Environmental Conditions

Ultrasonic devices should be mounted in a predictable environment

Vapor, condensing humidity, and other contaminates that change the speed of sound through air greatly effect the accuracy of the return signal

The most popular benefit  of through-air measurement  principles like Ultrasonic, Radar, or Laser measurement is the fact that the measuring signal never comes in contact with the product being measured. But if you think about  it, this ‘fact’ is not entirely accurate. Take Ultrasonics for example: When sound energy leaves the transducer, it travels through  air at 1,125  feet per second until it reaches its target (i.e. liquid surface).

Similar to all other “non-contacting” type of level measurement, at some point the measuring signal must come in contact with the liquid surface before it begins its return trip back to the sensor. This not only explains why the air quality between the sensor and liquid surface can be problematic, but also why the quality of the liquid surface needs to be accounted for. Every disturbance it picks up on its way down and back will disturb the actual level measurement information in the signal

It is important to understand that Ultrasonic transmitters will provide a sensible solution, when properly applied. Remember, the Ultrasonic transmitter is just as good as the echo it receives.

GUIDED WAVE RADAR (GWR) TECHNOLOGY

Guided Wave Radar (GWR) is a contacting level measurement method that uses a probe to guide high frequency, electromagnetic waves as they travel down from a transmitter to the media  being  measured.

GWR is based upon the principle of Time Domain  Reflectometry (TDR), which is an electrical measurement technique that has been used for several decades in various industrial measurement applications; among its first fields of application was the location of cable damage. In level measurement, however, TDR has only been used for a little over a decade.


With TDR, a low-energy electromagnetic pulse is guided along a probe. When the pulse reaches the surface of the medium being measured, the pulse  energy is reflected up the probe  to the circuitry which then  calculates the fluid level from the time difference between the pulse  sent  and the pulse  reflected. The sensor can output the analyzed level as a continuous measurement reading through its analog output, or it can convert the values into freely positionable switching output signals.


GWR is suitable for a variety of level measurement applications including:

Unstable Process Conditions

Changes in viscosity, density, or acidity do not effect accuracy

Agitated Surfaces

Boiling surfaces, dust, foam, vapor do not effect device performance

Recirculating fluids, propeller mixers, aeration  tanks

Extreme Operating limits

GWR performs well under extreme  temperatures up to 600ºF (315ºC)

Capable  of withstanding  pressures up to 580 PSIG (40 Bar)

Fine Powders & Sticky Fluids

Vacuum tanks with used cooking oil

Paint, latex, animal fat and soy bean oil

Saw dust, carbon black, titanium tetrachloride, salt, grain

One of the most common misconceptions of GWR is the effects of product build-up on the probe.  One would think that if you have a mass of product stuck to the probe, or a coating of product throughout the entire probe length, that the signal would misidentify the true liquid surface.

This in fact is not the case with advanced GWR technology. The radar signal of GWR has a very large detection area around the probe covering 360˚ of area over several feet of coverage.  When this pulse energy comes in contact with a mass of product on the probe, the signal is returned and analyzed to see if it is the true liquid level.

Since the liquid level always has a larger signal return than the smaller mass that is sticking on the probe, the liquid surface is easily identifiable. The advanced algorithms developed over the last decade have made this contacting form of level measurement the ideal solution  for even  the stickiest of fluid applications.

Advantages of GWR in the level industry are endless.  Unlike older technologies, GWR offers measurement readings that are independent of chemical or physical properties found in the contact media. Additionally, GWR performs equally well in liquids and solids.

The chart below compares some important features between Ultrasonic and Guided Wave Radar




Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...