Manual Level Measurement

 Although the scope of the document is about fixed installed measuring instruments, manual measurements should be at least discussed briefly. Manual measurements are still quite often used as they are perceived as ‘low cost’ (at least initial), do not require cabling or power and are often used for during commissioning, or verification of installed instrumentation.

Manual Level Measurement

There are three mains manual measurement principles used:

tape, ruler or dip stick

sight glass

portable electronic.

Both of these manual methods make use of a graduated measurement tape, ruler or dipstick, to read the level and/or interface.

 Tape, ruler and dipstick

This measurement is typically used on large tanks.

Figure – Typical gauge tapes, bobs and a water gauge bar (Source: API MPMS Ch. 3.1A)
Figure – Photo of typical dip tape as use on bulk storage tanks

Image Courtesy : Rigana

A ruler or dipstick is typically used for relative small tanks. A practical limit is 2 to 3 metres height max. In some area’s/countries also so called ‘slip tube’ gauges are used for on LPG rail tankers.

NFPA 58 describes slip tube gauge as a “A variable liquid level gauge in which a relatively small positive shutoff valve is located at the outside end of a straight tube, normally installed vertically, that communicates with the container interior.” A slip tube is basically a ‘dip stick’.

Figure – Example of dip opening of foreground station (petrol station)

On clear liquids and very light products which easily evaporate, including water, often a coloring paste is used. The paste changes color when in direct contact with the liquid.

For water detection which is often called ‘water‐finding’ rule to detect a level is recommended. Water finding rules are typically made of brass with alternating transparent plastic sections, which allows seeing where the paste has discolored when measuring water in opaque oils

Sight glass
For closed tanks, and products which are toxic, easily evaporate or are flammable, often a sight glass is used.

The sight glass is typically installed as part of a ‘chamber/cage’. It can either be a transparent piece of piping or a metal enclosure with typically a hardened flat glass view pane.

The tank connections often have block valves, which allow maintenance on the sight glass and sight glass body. Some sight glass designs also incorporate drain valves which allows cleaning (‘flush’) the system.


Figure – Sight glass on fuel tank

Reflex gauges are a special form of sight glass gauges, and use optical refraction and reflection for an improved visibility of interfaces in and between vapour/gas and liquid zones.

Figure (Left) Example of sight glass construction for pressurized application
Figure (Middle) Sight glass installed on LPG horizontal bullet tank

Figure (Right) High pressure sight glass with graduated scale

Is some specific areas and equipment (steam generators, boilers, power generation), the use of sight glass type level gauges may also be mandatory to fulfill the design code (e.g. ASME I).

Sight glass may also be useful where direct vision of the fluid is relevant.

Portable electronic gauging
Portable electronic gauging can measure the level of ullage and the oil–water interface. Portable electronic gauging is suitable for open and closed applications. Closed gauging operations will generally require the portable electronic gauging to be used in conjunction with a compatible vapour lock valve.
Figure – Portable electronic gauging system with vapour lock valve

Representative measurements of the temperature of the tank contents may also be measured with the portable electronic gauging. This temperature measurement permits to convert the observed volume to a standard volume measurement.

Limitations
Tape, ruler and dipstick
Tape, ruler or dipstick can only be used when the tank is not pressurized and the tank contents are considered to be safe (i.e. not toxic, dangerous and do not pose an environmental issue).
Figure – Necessary safety precautions (PPE) on toxic products

Sight glass
Sight glasses cannot be used for tanks containing sediment or solids, as the connection might become blocked.

Use of sight glasses can be considered for interface measurement also, provided the interface layer is clearly visible.

Sight glass installation is also possible on pressurized tanks but sometimes perceived as a safety risk.

On tanks which also contain solids, the reading of the sight glass can be unreliable as result of blockage. For these applications strict procedures for periodic flushing the sight glass and connections should be considered.

Sight glass systems have the limitation of where the level can be between glasses and in the ‘brass’ area and hence it is difficult to understand where the level is.

Sight glasses require regular maintenance and cleaning. The presence of some hydrocarbon liquids can cause staining and this can make it difficult to ascertain where the true level actually is placed.

Portable electronic gauging
Safety and environmental regulations may restrict tank gauging operations which can result in the release of hydrocarbons or other volatile organic compounds into the atmosphere. In these circumstances, it will not normally be feasible to use traditional open gauging procedures via an open gauge hatch or gauging access point.


Figure – Portable electronic gauging system with vapour lock valve

Selection
For all toxic, pressurized and dangerous products, ‘closed’ solutions are preferred.

If manual methods are to be used, the safe use should be covered by procedures and formal training.

Calibration and configuration
For applications where the accuracy is of importance, the graduated scale on tape, dip stick or sight glass can be calibrated.

It is important to realize that it is always critical to use the correct datum point on the particular tank. This datum point can be a ‘dip’ plate on the bottom or a clear marked mechanical provision on or in the tank nozzle.

Sight glasses can be adjusted by shifting the graduated scale.

The portable electronic gauging sensor is calibrated once at the factory and does not require subsequent calibration.

Source : International Association of Oil & Gas Producers


Comments

  1. Great job for publishing such a nice article. Your article isn’t only useful but it is additionally really informative. Thank you because you have been willing to share information with us. Aqua Analytics

    ReplyDelete
  2. I'm really inspired together with your writing skills and also with the layout for your weblog. Thanks for sharing this blog here. Oil Tank Level gauge

    ReplyDelete

Post a Comment

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...