Skip to main content

Types of Thermowells

 Thermowell is provided to protect the temperature sensor from mechanical damage and corrosion.

An extremely sturdy design may increase the life of the sensor but may lead to a poor response. Similarly, a delicate design will have poor life but will improve the response time. Therefore, a proper balance needs to be struck.

For given process parameters, we can arrive at an optimum Thermowell design considering aspects such as temperature, pressure, fluid velocity and corrosion. Such designs will conform to ASTM PTC 19.3.

The Thermowell material can be brass, SS304, SS316, SS316L, SS310, Inconel® 600, Incoloy® 800, Monel®, Hastelloy® depending upon the process parameters and type of fluid.

Types of Thermowells

  1. Bar Stock Threaded (BT) (Process threads NPT, BSP or Metric)
  2. Bar Stock Flanged (BF) (Flanges as per ANSI, BS or DIN )
  3. Bar Stock Weld In (BW)
  4. Fabricated Threaded (FT)
  5. Fabricated Flanged (FF)
  6. Fabricated Weld In (FW)

Barstock Thermowell is normally offered up to an insertion length of 600mm.

Fabricated Thermowells are recommended above 600mm. If required, insertion length can be determined by performing wake frequency calculations, in accordance with PTC 19.3.

Welding (tig welding process) of the Thermowell is performed by professional and approved welders following practice laid down in the ASME code and weld joints can be tested up to 600 kg/cm.

Bore concentricity within 10% of wall thickness can be checked by radiography or ultrasonic method. Special material tests such as an ultrasonic test for flaw detection are also available.

Bar Stock Threaded Thermowell

  • Bore in mm (d)
  • Cold End Diameter in mm (D2)
  • Hot End Diameter in mm (D1)
  • Insertion Length in mm (U)
  • Tip Thickness in mm (t)
  • Extension Length in mm (T)
  • Dia of Barstock in mm (D)
Bar Stock Weld-In Thermowell
Bar Stock Flanged Thermowell
Fabricated Weld-In Thermowell
Fabricated Threaded Thermowell

Fabricated Flanged Thermowell
Special Thermowells
Van Stone Type Thermowell
For high-pressure applications and where welding is to be avoided, Van Stone design thermowells are used. These are machined from single bar stock, sandwiched between the nozzle flange and cover (companion) flange.

The OD of the machined portion corresponding to the raised face portion of the flange. Wake frequency calculations (in accordance with PTC 19.3) are performed where ever data is made available and are essential in order to suggest appropriate dimensions of thermowell.

Welding Operation
Thermowells are often with welded design. Welding is the most critical operation as improper welding can cause the failure of welding in process in the form of corrosion & crack. This is particularly serious when thermowell is being used for critical applications such as Hydrogen, H2S or explosive media.

Nozzle suitable for Collar Design Thermowell
Engineers many times face a lot of problems in installing collar design thermowells at the site due to the following reasons:

a) Nozzle ID is inconsistent.

b) Some weld material penetrates inside Nozzle blocking entry of collar.
To solve these problems we supply collar design thermowells along with the matching nozzle. The engineer only has to weld the weldolet at the site.

Thermowell Material Selection Guide















Comments

  1. Really helpful down to the ground, happy to read such a useful post. I got a lot of information through it and I will surely keep it in my mind. Keep sharing. If you are looking for some useful data and information regarding 316 Stainless Steel Round Bar then visit Great steel & metals.

    ReplyDelete
  2. Thanks for such a pleasant post. This post loaded with lots of useful information. Keep it up. If you are looking for the best information and suggestions related to stainless steel flange bolts then visit nickelalloysonline.

    ReplyDelete

Post a Comment

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...