SWAS Analyzers Questions and Answers

 Steam and water analysis system (SWAS) is a system dedicated to the analysis of steam or water. In power stations, it is usually used to analyze boiler steam and water to ensure the water used to generate electricity is clean from impurities which can cause corrosion to any metallic surface, such as in boiler and turbine.

What is SWAS ?

SWAS stands for Steam & Water Analysis System. This system is useful for Power Plants that run on steam. The quality of steam that is used by these power plants is of utmost importance – it is like monitoring cholesterol in human body. Various contaminants that might exist in steam can prove very harmful to the turbine, to the boiler, to the piping etc.

SWAS effectively monitors these parameters (such as pH, Conductivity, Silica, Sodium, Phosphates, Dissolved Oxygen etc.) and thus helps in maintaining healthy operation of a power plant. In all power plants in India that work with more than 90% efficiency – you will always find a well engineered, well maintained SWAS.

A typical SWAS comprises of

(A) a Sample Conditioning System (some call it Sampling System) where the Temperature, Pressure & Flow of sample if conditioned and regulated and

(B) an analyzer panel where all the on-line analyzers are located.

The sensors of these analyzers receive the sample conditioned by the sample conditioning system and send signals to analyzers. The analyzers in turn send these signals to respective parameters in 4 to 20mA signal which is finally delivered to the plant DSC or PLC.


Importance of SWAS
In any power plant running on steam, the purity of boiler feed water and steam is absolutely crucial; especially to steam turbine, steam boiler, super heater, condenser and other steam equipment.

To prevent damage of steam turbine, steam boiler and other apparatus due to scaling and corrosion, on line steam and water analysis of critical parameters such as pH, Conductivity, Dissolved Oxygen, Silica, Sodium, Phosphate etc. is a must.

The steam can be as hot as 560ºC. The pressures can be as high as 250 bar. To keep the power plant up and running, with minimum erosion and corrosion of steam turbine, steam boiler and condenser, we have developed fully integrated Steam and Water Analysis Systems (SWAS) that provide exact, precise measurements on all these critical parameters.

A good SWAS necessitates efficient sample cooler for water sampling, steam sampling or process sampling problems.

What do the standards generally say about the important components of SWAS?
Sample Cooler :
This should be preferably a coil-in-shell type of heat exchanger that provides contra-flow type of heat exchange. It should achieve an approach temperature within + 50 C.

The pressure drop on the c.w. side should be minimum. Should have necessary blow-down arrangement for the coolant for periodic maintenance. There should be provision of shell relief valve on the cooler itself.

Pressure Regulator (PR) :
This should provide not only pressure reduction but pressure regulation also, irrespective of upstream fluctuations. Especially at low flow rates or low inlet sample pressures, the PR should still give regulated output.

If the pressure reducing device is not capable of doing so, it is possible that some of the analyzers will starve, which defeats the purpose of having a sampling system.

The pressure regulator also should provide tight shut-off if downstream blockage arises.

The pressure reducing device should not have large dead volume in the body which can entrap particulate and other species, causing ionic exchange and degradation of sample and therefore leading to incorrect readings.

What can happen if you don’t have SWAS?

Do you know that 50% of forced power plant shutdowns can be attributed to impurities and other cycle chemistry problems?

A well designed SWAS package directly attacks these problems. People with good knowledge, experience and expertise prefer on-line monitoring of all the necessary parameters involved in plant cycle chemistry. You will always find a properly maintained SWAS in all power plants that are running at 95+ PLF / PAF.

Is SWAS mandatory in Thermal Power Plants ?

The very reason to have SWAS package in a thermal power station is to have a constant watch on problems associated with corrosion, impairment of heat transfer, dosing optimization, plant effluents, scaling, boiler blow down etc. It is important for the health of a power plant.

Where SWAS is used ?

Anyone who is using steam for his or her process and the quality of steam is critical, one should look for SWAS to provide a good solution. Apart from Power industry there are many other industries which are dependent on quality of steam for their end product. All these can benefit from SWAS.

Why do sample coolers fail?

One of the main reasons for sample cooler failure has been observed to be the failure of the sample coil due to stress corrosion cracking. Here is a detailed analysis of this problem :

Root Cause:

If the chloride content of cooling water is high as per cooling water specifications (i.e. more than 35ppm), we don’t recommend use of SS316 material for sample cooler coil.

The reason being, sample steam entry is at a higher temperature and pressure. In such cases sample coil may be subjected to inter-granular corrosion resulting in stress corrosion cracking.

Due to high hardness of cooling water there is formation of sludge and scales on sample cooler coils causing the above problems.

Scales and sludge in the sample cooler is a non conductive layer formed on the water side of sample cooler coil causing reduced heat transfer efficiency

Symptoms:

Failures in the coil are characterized by a thick wall, brittle-type crack. This may be found at locations of higher external stresses, such as near attachments.

Causes:

SCC is most commonly associated with austenitic (stainless steel) materials and can lead to either transgranular or intergranular crack propagation in the tube wall. It occurs where a combination of high-tensile stresses and a corrosive fluid are present. The damage results from cracks that propagate from the ID.

The source of corrosive fluid may be carried over into the super heater from the steam drum or from contamination during boiler acid cleaning, if the super heater is not properly protected. Other sources include scaling, deposition, mud and impurities that can travel in the pipelines during startups

Problems faced by the user:

  1. Scaling and sludge formation on  the water side of sample cooler
  2. Loss in sample cooler efficiency causing higher sample temperature at outlet of sample cooler

Use of special material like Inconnel 625 reduces formation of non conductive layer, but, it cannot avoid it 100%.

Thus following are remedies to this problem:

  1. DM Water is recommended for use as cooling water.
  2. If it is not possible, softened water with very low hardness (CaCO3 & MgCO3) can be used, to reduce scaling problems
  3. Proper maintenance and periodic cleaning of sample cooler coils is must in cases where D M Water is not used for cooling purposes

To make maintenance easy:

  1. All coils in our coolers are removable – so if there is damage, you don’t have to replace the entire cooler – just coil replacement is possible.
  2. The shell is removable without the need to dismantle the sample cooler. This facilitates cleaning of coils in a very simple way.
  3. For routine maintenance, a drain plug is provided at the bottom of the shell. This facilitates quick cleaning of the shell, as the mud / sediments settled at the bottom can be easily removed.

Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...