Magnetostrictive Level Transmitter Calibration Procedure

 Magnetostrictive Level Transmitter is a two wire loop powered instrument which transmits an analog 4-20mA loop current in proportion to the measured liquid level in the tank.


This type of level transmitter uses a special type of sensor probe with a magnetic float to sense the level. The float is selected such that it’s specific gravity is lighter than the liquid whose level is to be measured, so that it always floats on the liquid.


Magnetostrictive Instrument


Image Courtesy: ekotech

This sensor probe with magnetic float is inserted into a tank or briddle where the liquid level to be measured. The float raises or falls as per the liquid level in the tank.

This level transmitter operation is based on the principle of magnetostrictive technology.

The transmitter generates a high-current pulse and transmitted down to the sensor probe, this is called as wave guide. This wave guide produces a circular magnetic field around the sensor probe (wire). The float also carries a permanent magnet in it.

When this wave guide reaches the permanent magnet in the float, a torsional force is produced, twisting the wire and producing a torsional wave (shown in below figure). This torsional wave travels back to the transmitter. By measuring the time of flight of the torsional wave (time duration), we can easily calculate the tank level.
As the tank level changes, the float tracks the change and continuously activates the sensor in the tube. The electronics in the transmitter process the changing signal and generates an 4-20 mA output corresponds to the measured level.

The Magnetostrictive Level Transmitter can also be used to measure the interface level between two fluids.

Calibration
The Magnetostrictive Level Transmitter calibration carried out using two ways.

  1. Using Push buttons on the transmitter
  2. Using HART Communicator
Calibration using Pushbuttons
Setting the 4mA or LRV

  • Move the float to the desired 0% level reference.
  • Enter the calibration mode by pressing the UP & DOWN buttons.
  • Go to the Zero trim using the push buttons and set the output at 4.00mA.
Setting the 20mA or URV

  • Move the float to the desired 100% level reference.
  • Enter the calibration mode by pressing the UP & DOWN buttons.
  • Go to the Span trim using the push buttons and set the output at 20.00mA.
Note: The push buttons sequence may vary from manufacturer to manufacturer, refer the technical manual.

Gauge Mounted Magnetostrictive Level Transmitter Calibration
In this case, both level gauge and level transmitter are mounted on the same unit.

  1. Connect the magnetostrictive level transmitter as shown in the above image.
  2. Take the datasheet of the particular level transmitter. In the datasheet, you will find lower range value (4mA) and upper range value (20mA). Example: LRV is 5 inch and URV is 20 inch. If you don’t have the datasheet then manually measure the length using the tape.
  3. Level gauge and transmitter is mounted on the same unit, you can use the level guage readings as reference during level chamber filling.
  4. Now fill the level chamber with the water upto the 0% reference level and read the transmitter readings using the HART communicator.
  5. Transmitter has to show 0% level, if not then do zero trim using the HART communicator.
  6. Now fill the level chamber with the water upto the 100% reference level and read the transmitter readings using the HART communicator.
  7. Transmitter has to show 100% level, if not then do span trim using the HART communicator.
  8. During the calibration, multimeter may be used to note down the corresponding loop current.
Note: We can also use the same process liquid instead of water for the calibration, if it is not hazardous.

Direct Mount Magnetostrictive Level Transmitter Calibration
In this case, there is no level gauge available.

  1. Connect the magnetostrictive level transmitter as shown in the above image.
  2. Take the datasheet of the particular level transmitter. In the datasheet, you will find lower range value (4mA) and upper range value (20mA). Example: LRV is 5 inch and URV is 20 inch. If you don’t have the datasheet then manually measure the length using the tape.
  3. Move the float to the 0% reference level and read the transmitter readings using the HART communicator.
  4. Transmitter has to show 0% level, if not then do zero trim using the HART communicator.
  5. Move the float to the 100% reference level and read the transmitter readings using the HART communicator.
  6. Transmitter has to show 100% level, if not then do span trim using the HART communicator.
  7. During the calibration, multimeter may be used to note down the corresponding loop current.
Note:

The float was designed to operate at a specific gravity of process medium which will be there in the tank. During our calibration, if we use water for the float movement, then there will be some error when the transmitter taken inline. As the process medium and water have different specific gravities.

The error may be positive or negative as it depends on your float specifications. It is recommended to use a attached level guage reading for making the reference 0% and 100% level. In case if there is no attached level guage then it is best to disassemble the unit and manually move the float to 0% and 100% during the calibration.



Comments

  1. I admire this article for well-researched content and excellent wording. Thank you for providing such a unique information here. Oil Tank Level gauge

    ReplyDelete

Post a Comment

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...