How to Reduce the Control Valve Noise?

 There has been so much research going on for controlling the noise generated by control valves but before that one must understand how this noise is generated in the valve. Still, very limited ways are available to control the valve noise.

The control valve noise problem may involve any or all of the source-path-receiver elements. Among them, source and path treatment is widely used for valve noise reduction and we will discuss them.

Direct Approach (Source Treatment)
Reduction of the acoustic energy at the source is the most desirable approach and widely used.

Generally, low noise valves or low noise cage trim valves as shown in the below figure consist of multiple small orificial elements. Most quiet valve uses the concept of distributing the acoustic energy into smaller flow paths.
The reduction of acoustic energy is accomplished by minimizing the effect of the shock wave and its strength.

Redistribution involves shifting of acoustic energy into a high-frequency range. Because of the smaller flow paths, the plugging of the solid material trapped inside is the most common problem faced while using this technique.

For manufacturing such valves we need sophisticated techniques hence they are very expensive compared to conventional valves.

In addition, low flow capacity is an inherent characteristic of most wall noise suppressor.

Another method of reducing valve noise generation is by reducing the pressure drop across the wall orificial elements through several stages. Each stage consists of a fixed restriction which allows the flow to defuse or expand this type of fixed restriction is usually placed immediately downstream of the valve outlet and can take the form of the plate with multiple orifices.


 
The device shown in the below figure is commonly referred to as a downstream expansion plate or diffuser because of the small multiple orifices it is susceptible to clogging due to solid particles.
Indirect Approach (Path Treatment)
Typical part treatment consists of the use of inline silencers heavy-walled piping acoustical insulation and sound enclosures. The principle of the path treatment is to reduce the propagation and transmission of sound to the external sound field in general there are two types of silencer resonator and absorptive.

Resonator silencer usually consists of a series of broadly tuned Chambers which usually is effective only over a narrow frequency band.

The absorptive silencer absorbs the acoustical energy by the use of sound-absorbing materials, linings, or baffles inside the silencers. This type of silencers can provide attenuation over a wide frequency range and is most widely used.

It is well known that the wall noise is radiated throughout the downstream piping and is considered to be a line source. Increasing the pipe wall thickness is a method that can be used to increase sound transmission loss or to reduce the overall noise radiation.

Another widely used method is the application of Acoustical insulation or pipe lagging it has been found that the pipe lagging can be very effective provided it is correctly applied.

It has been recommended to use 50 mm thick insulation for general lagging purposes. It should be noted that both heavy-walled piping and lagging are localized methods in that they become ineffective once the treatment is terminated.

Enclosing the valve body and downstream piping by sound barrier or enclosure can be effective provided that acoustic leaks due to flanking paths are eliminated also this method can be economical if the length of the piping to be enclosed is minimal.






Comments

  1. You have shared such a wonderful post which about valve noise. Thanks for such information. Keep it up. Fire Smoke Detector

    ReplyDelete

Post a Comment

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...