General Specification of Thermowell

 Here we shall see detailed specifications of Thermowells.

Thermowells shall be provided with every temperature element and shall be machined out of bar stock up to length 600mm and with SS 316 material as a minimum.

Thermowell Specification

The design of thermowell shall be according to standard drawings for flange type up to 600# ANSI.

Above 600#, the contractor may use their proven design for a specific application

Flange material SS 316 as minimum

In corrosive and abrasive services Stallited thermowells are used.

There shall be no air gap between the bulb and thermowell to ensure a rapid response.

Internal diameter shall be suitable for temperature elements.

In very high-pressure applications, the welded type of thermowell is used.

The inside diameter of the finished thermowell shall be concentric with all other diameters with a tolerance of 0.2 mm.

The thermowell shall be machined and rifle drilled to a smooth finish after welding and heat treatment. The surface finish of the stem shall be 10-15u inch (0.254-0.381 microns).

Built-up thermowells shall be used in low pressure and low-velocity services like in fired heaters and also where thermowell immersion lengths greater than 600 mm is required. In all such cases, all-welded joints shall undergo 100% radiography testing. For joints where radiography is not possible, a dye penetration test may be carried out. Orifice dimensions and machining tolerances should be according to BS 1042 Part 1 standard.

Thermowells shall be assessed for resonance effects. Where Thermowells are installed in lines subjected to high fluid velocities (exceeding 6 m/s for liquids and 120 m/s for vapors/gases), combined stress and frequency calculation shall be carried out by a proven method. In case the thermowell design fails vibration analysis, an alternate design may be used by the contractor. All such designs along with calculations shall be submitted for the purchaser’s review.

Immersion Length `U’ of thermowells shall be as follows:
Immersion length is based on a 200 mm length between the flange face and the inner wall of the pipe. In special applications, where thermowell nozzle sizes are larger or where the temperature is to be measured at any specific location, the contractor shall decide the immersion length based on actual requirements.

Any pipeline less than 4″ nominal bore shall be blown to 4″ size to install thermowell.

Thermowells with lagging extension are used in pipe systems and on vessels, where these are insulated. The length of the lagging is determined by the thickness of the insulation. The standard lagging extension is 89 mm (3″) except for thermowells with an insertion length of 63.5 mm (2.5″), where the lagging extension is 60 mm (2″). Other lagging extensions are available on request with multiple of 89 mm (3″) to provide for standard instrument insertion length.

The thermowells are provided with 4 main methods of process connections: they are

  • Threads,
  • flanges,
  • weldings, and
  • clamp.
Threaded thermowells are the most commonly used wells, because of the low cost and the ease of installation.

Threaded thermowells are not recommended for pressure above 70 bar (1000 psi).

The standard thread sizes are 3/4″ and 1″ NPT.

Flanged thermowells are used, when the pipe spec. calls for flange executions and at elevated pressure. The thermowells are supplied with flanges according to B 16.5 with raised face or ring type joint for pressure classes from 150 – 2500 lbs.

The flanged thermowell may either have the flange welded on the shank (stem), or the flange and shank may be forged as an integrated unit for use in severe service conditions.

Flange sizes are : 1″, 1 1/2″, and 2″.

Weld in thermowells are used at extreme pressure and temperature service conditions, and when ASME codes require welded connections.

The weld-in type thermowell is a low-cost item, but the disadvantage is that the well is not removable for inspection or replacement.

The standard weld in size is 38 mm (1 1/2″), 26.9 mm (3/4″ nominal pipe size), or 33.4 mm (1″ nominal pipe size).

Comments

Popular posts from this blog

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...

What is a Torbar? – Averaging Pitot Tubes

 The Torbar is employed for flow measurement of liquids, gases, or steam in circular, square, or rectangular section ducts for large flow rates. The Torbar is an insertion type multi-port self-averaging primary sensor for flow measurement. Torbar TORBAR is a set of Pitot tubes mounted on a bar across the pipeline with no moving parts. An averaging Pitot tube is a technology, while TORBAR is a manufacturing brand name. There are several brands available in the market with VERABAR, ANNUBAR, etc. Averaging Pitot Tube Principle Purpose Averaging Pitot tube can be employed when the average velocity of the flow profile, rather than the velocity in a specific point in the cross-section is desired. Averaging Pitot Tubes Principle It measures the differential pressure between the static pressure tap and the tap of full pressure of a stream. Thus such magnitude of differential pressure is directly proportional to the square of the flow rate. Working The TORBAR is designed in such a way that ...

Dissolved Oxygen Analyzer Working Principle

 What is dissolved oxygen ? Dissolved oxygen refers to oxygen dissolved in water. Its concentration is expressed as the amount of oxygen per unit volume and the unit is mg/L. Biologically, oxygen is an essential element for respiration of underwater life and also acts as a chemical oxidizer. The solubility of oxygen in water is affected by water temperature, salinity, barometric pressure, etc. and decreases as water temperature rises. Measurement of dissolved oxygen by the membrane electrode method The membrane electrode method measures a diffusion current or reduction current generated by the concentration of dissolved oxygen or partial pressure of oxygen to obtain the concentration of dissolved oxygen. This method is not affected by the pH value of water being measured, oxidation and reduction substances, color, turbidity, etc. and the measurement method offers good reproducibility. When a sensor is inserted into water, an air layer forms on the membrane (Teflon membrane). The ox...