Skip to main content

General Specification of Thermowell

 Here we shall see detailed specifications of Thermowells.

Thermowells shall be provided with every temperature element and shall be machined out of bar stock up to length 600mm and with SS 316 material as a minimum.

Thermowell Specification

The design of thermowell shall be according to standard drawings for flange type up to 600# ANSI.

Above 600#, the contractor may use their proven design for a specific application

Flange material SS 316 as minimum

In corrosive and abrasive services Stallited thermowells are used.

There shall be no air gap between the bulb and thermowell to ensure a rapid response.

Internal diameter shall be suitable for temperature elements.

In very high-pressure applications, the welded type of thermowell is used.

The inside diameter of the finished thermowell shall be concentric with all other diameters with a tolerance of 0.2 mm.

The thermowell shall be machined and rifle drilled to a smooth finish after welding and heat treatment. The surface finish of the stem shall be 10-15u inch (0.254-0.381 microns).

Built-up thermowells shall be used in low pressure and low-velocity services like in fired heaters and also where thermowell immersion lengths greater than 600 mm is required. In all such cases, all-welded joints shall undergo 100% radiography testing. For joints where radiography is not possible, a dye penetration test may be carried out. Orifice dimensions and machining tolerances should be according to BS 1042 Part 1 standard.

Thermowells shall be assessed for resonance effects. Where Thermowells are installed in lines subjected to high fluid velocities (exceeding 6 m/s for liquids and 120 m/s for vapors/gases), combined stress and frequency calculation shall be carried out by a proven method. In case the thermowell design fails vibration analysis, an alternate design may be used by the contractor. All such designs along with calculations shall be submitted for the purchaser’s review.

Immersion Length `U’ of thermowells shall be as follows:
Immersion length is based on a 200 mm length between the flange face and the inner wall of the pipe. In special applications, where thermowell nozzle sizes are larger or where the temperature is to be measured at any specific location, the contractor shall decide the immersion length based on actual requirements.

Any pipeline less than 4″ nominal bore shall be blown to 4″ size to install thermowell.

Thermowells with lagging extension are used in pipe systems and on vessels, where these are insulated. The length of the lagging is determined by the thickness of the insulation. The standard lagging extension is 89 mm (3″) except for thermowells with an insertion length of 63.5 mm (2.5″), where the lagging extension is 60 mm (2″). Other lagging extensions are available on request with multiple of 89 mm (3″) to provide for standard instrument insertion length.

The thermowells are provided with 4 main methods of process connections: they are

  • Threads,
  • flanges,
  • weldings, and
  • clamp.
Threaded thermowells are the most commonly used wells, because of the low cost and the ease of installation.

Threaded thermowells are not recommended for pressure above 70 bar (1000 psi).

The standard thread sizes are 3/4″ and 1″ NPT.

Flanged thermowells are used, when the pipe spec. calls for flange executions and at elevated pressure. The thermowells are supplied with flanges according to B 16.5 with raised face or ring type joint for pressure classes from 150 – 2500 lbs.

The flanged thermowell may either have the flange welded on the shank (stem), or the flange and shank may be forged as an integrated unit for use in severe service conditions.

Flange sizes are : 1″, 1 1/2″, and 2″.

Weld in thermowells are used at extreme pressure and temperature service conditions, and when ASME codes require welded connections.

The weld-in type thermowell is a low-cost item, but the disadvantage is that the well is not removable for inspection or replacement.

The standard weld in size is 38 mm (1 1/2″), 26.9 mm (3/4″ nominal pipe size), or 33.4 mm (1″ nominal pipe size).

Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution : A

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Electroma

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. ClO2