Different Types of Turbine Protective Devices

 This article provides the list of different types of Turbine Protective Devices like turbine over speed trip, low lube oil pressure, axial displacement, turbine temperature and turbine vibrations.


Turbine Protective Devices

  • Tripping Device
  • Low Lube Oil Pr.
  • Over Speed Trip
  • Low Vacuum
  • SOV for remote tripping
  • Hi/Lo Extrn. Pr.
  • Casing Expansion
  • Extrn./Exhaust Temp Differential Expansion
  • Generator Protection
  • Axial Displacement
  • Manual/Remote Trip
  • Bearing Vibrations
  • Casing/Rotor Temp.
  • Bearing Temperatures
Tripping Device

When ever the turbine is to be tripped , the Governing oil pressure is drained by tripping device. Thus pressure in front of stop valve piston disc and control oil pressure falls, resulting in closure of stop valve and control valves.

Over Speed Trip

The over speed protection is formed by three independent sensors of turbine speed evaluation that act through a selection of the output signal two of three after exceeding a set value of security speed for an immediate impulse for closing of the ESV within less than 30ms.


Magnetic Pickup
A magnetic pickup consists of a permanent magnet, wrapped with a coil of a few thousands turns of fine enameled copper wire.

When discrete ferromagnetic object such as gear teeth or blades are passed through the probes magnetic field, the flux density is modulated. This induces AC voltages in the coil. One complete cycle of voltage is generated for each object passed.

The total number of cycles will be a measure of the total rotation, and The frequency of the AC voltage will be directly proportional to the rotational speed of the shaft.
Making and breaking of the flux lines induces an alternating voltage into the coil around the pole piece.

Each pulse is represented by a gear tooth passing by the MPU. The impedance of MPU is approximately 220 ohms.
PROXIMITOR (Eddy Current Probe)
The mechanical energy is transformed into electrical energy using the proximity Transducer system. The interface device used for this system is called a proximitor. It generates a radial frequency(RF) signal using an oscillator circuit.

The RF signal is transmitted from the probe coil which creates an RF field around the probe tip. When conductive material is present in the RF field, Eddy currents flow in the surface of that material.

Once the probe is close enough to cause eddy currents to flow in a conductive material the RF signal is affected in two ways.

Amplitude is minimum, when the Gap is less.
Amplitude is maximum, when the Gap is more.
If the target is moving slowly within RF field, the signal amplitude will increase or decrease slowly. Depending on the movement of target, the amplitude increase or decrease slowly or rapidly. This oscillatory movements of the target causes the RF signal to modulate.
This will be convert by demodulator and will give a AC signal (sine wave). If the target is oscillating (gap changing slowly or rapidly), the proximitors output also vary the DC voltage (AC) shown above by a sine wave.

If the probe is observing a vibration, the proximitor will provide both a DC (gap) and an AC (vibration) component in the output signal. The frequency response from 0 Hz to 10 kHz.

Casing Expansion
This is the measurement of Turbine Casing or Shell moves in relation to a fixed location usually measured with a LVDT (Linear variable differential Transformer). Case expansion is the Thermal growth of the machine case as It expands during machine startup and on line operations.

Thermal growth at different rates can cause internal rubbing between rotating and stationary parts of the machine.

The case expansion transducer system uses the LVDT to measure the machine Case thermal growth.


 
A rod on the LVDT connects to the machine. As the machine case grows, the rod moves inside the LVDT. This causes a change in the signal in the LVDT.

Range:- 0 ~ 25mm; Trip:- 20mm

Rotor Expansion
During turbine startup, extra care must be taken to ensure that the case has been properly heated and expanded sufficiently to prevent contact between the rotor and the case.

For this Eddy probe transducer will generate a high frequency oscillating RF signals that is sent through the extension cable to the pickup tip. The pickup tip having a wound coil of fine wire, radiates a electromagnetic Field, as the radiated field is bisected by the rotor surface.

As the rotor surface moves closer to the pickup tip, a greater amount of eddy currents are created Proportional to the gap between the surface and the pickup tip. The signal sensor contains a demodulator which measure the increase in eddy currents, and generates an equivalent DC voltage proportional to the gap.

Rotor Expansion on a turbine is the absolute measurement of the rotor’s axial thermal growth with respect to the turbine’s foundation.

Differential Expansion
This is very important parameter receiving much attention during turbine startup and warming. This parameter measures how the turbine rotor expands in relation to the turbine shell or casing.

The difference between Casing expansion & rotor expansion is called differential expansion. It is the relative measurement of the rotor’s axial thermal growth with respect to the casing.

Differential Expansion on a turbine is the relative measurement of the rotor’s axial thermal growth with respect to the case. Casing expansion with respect to turbine’s foundation. Rotor expansion with respect to turbine’s foundation. Rotor expansion with respect to the casing is differential expansion

Range:- -4mm to 6mm

Alarm :- +2.30mm & -1.60mm

Trip:- +3.00mm & -2.50mm

Key Phasor
A transducer that produces a voltage pulse for each turn of the shaft, called the “KeyPhasor” signal. It produces a voltage pulse once each revolution.

Phase or phase angle, is a measure of the relationship of how one vibration signal relates to another vibration signal and is commonly used to calculate the placement of a balance weight.

This signal is used primarily to measure Shaft rotative speed and serves as a reference for measuring vibration Phase lag angle.

The keyphasor transducer is typically a proximity probe. The Keyphasor is a very useful tool when diagnosing machinery problems.

The standard scale factor is 200mV/mil or 7.87mV/um

1 mil = 25.4 microns

Rotor Axial Displacement

Two types of trips
  1. Rotor Axial Displacement
  2. Radial Vibration
The below table shows the alarm and trip values for bently nevada vibration measurement system.

S.NoDESCRIPTIONAlarmTrip
1Key Phaserxxxxxx
2Axial Displacement+/- .5mm+/- .8mm
4Rotor Front Bearing120u180u
7Rotor Rear Bearing120u180u
8Gear Box Pinion Bearing100u180u
15Gear Wheel Bearing100u150u
16Alternator DE Bearing100u180u
19Alternator NDE Bearing100u180u
20Turbine Casing Expansion20mm25mm
21Turbine Differential Expansion;  Towards probe+2.3mm+3mm
22Turbine Differential Expansion;  Away from Probe-1.6mm-2.5mm
Bearing Temperatures
Temperature of bearings is a measure of the how hot a bearing is operating. It may be due to overloading, misalignment, improper lubricant pressure and/or flow.

Nearly all turbine generator bearings were originally installed with bearing temperature sensors. These sensors may be thermocouples or RTDs. Any bearings that was not originally equipped with temperature sensors can be retro-fitted to accept thermocouples or RTDs.
TURBINE TRIP- TEMP
DECRIPTION – Siemens GovernorI / OSETPOINT
TYPEALARMTRIP
TURB THRUST BRG TEMP BTM NEGT / C110120
TURB BRG TEMP FRONTT / C110120
TURB BRGTEMP REART / C110120
GB PENION DE BRG TEMPRTD100110
GB PENION NDE BRG TEMPRTD100110
GB WHEEL DE BRG TEMPRTD110120
GB WHEEL NDE BRG TEMPRTD100110
GEN FRONT BRG TEMPRTD8590
GEN REAR BRG TEMPRTD8590
Generator Protection
  • Bearing and Winding Temperature
  • Earth fault Protection
  • Reverse/Low Forward Power
  • Over Voltage / Under Voltage
  • Over Frequency / Under Frequency
  • Over Current
  • Differential
  • Neutral displacement
  • Negative phase sequence
Note : Alarms and Trips Values may change from equipment to equipment.









Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution : A

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Electroma

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. ClO2