Control Valve Recommended Practices for Harsh Process Conditions

 Here we shall see recommended practices for selection of the control valve for harsh process conditions.

Control Valve Recommended Practices

 
  • The process design conditions should be as per the ANSI pressure rating and the material of the valve should be selected as per piping specifications for a particular project. The valve end connections and pressure rating should, as a minimum, conform to the piping specification. The valve material shall be suitable for the process conditions.
  • Nickel alloy or stainless steel valve metallurgy should be specified for temperatures below -20 degrees F. High-pressure steam, flashing water applications, and boiler feed water service where differential pressures exceed 200 psi may require harder chrome-molybdenum alloys. Sour service valve materials must meet the requirements of NACE MR0175-90. Corrosive and erosive components even in trace quantities may affect the metallurgical choice of the valve.
  • Trim material can be as per manufacturer standard but in high-pressure services, it should be checked for cavitation, flashing, and other unwanted phenomenons.
  • Globe valves are usually accepted with flange type of end connection. For pressure rating above 900, they are generally butt welded. Threaded and welded end connections are not recommended for hydrocarbon services.
  • Flanged control valve bodies are available with either integral flanges (machined as part of the body casting or forging, or flanges welded to the body), or separable flanges (individually removable flanges that usually lock in place on the valve body by means of a two-piece retaining ring).
  • Flangeless valves have no flange connections as part of the valve body and are simply bolted or clamped between the adjoining line flanges. Long bolts used with flangeless valves can expand when exposed to fire and cause leakage. A fire detection shield and/or insulation are recommended. In addition, high-tensile strength bolting is required.
  • The valve body size should be no less than two pipe sizes smaller than the line size. Smaller valve sizes must be reviewed to make sure that line mechanical integrity is not violated.
  • Threaded seat rings should be avoided where possible because corrosion often makes removal difficult.
  • Bonnets should be bolted. Bolting material should comply with ASTM A193/194/320 and should be compatible with the valve body and bonnet.
  • Bonnet gaskets should be fully retained 316 SST spiral wound, with polytetrafloroethelene or graphite filler. Flat gaskets made from PTFE sheet stock are acceptable where conditions permit. Insert reinforcements should be 316 SST or other appropriate alloys, as required.
  • Packing boxes should be easily accessible for periodic adjustment.
The packing material should

(1) be elastic and easily deformable,

(2) be chemically inert,

(3) be able to withstand applicable process conditions,

(4) provide a degree of fire resistance,

(5) minimize friction, and

(6) reduce fugitive emissions to meet regulatory requirements.

The valve manufacturer’s packing temperature limits refer to the temperature at the packing box.

  • PTFE has excellent inertness, good lubricating properties, and is one of the most popular valve packing materials. It may be used in solid molded, braided, or turned form (Vrings) or as a lubricant for asbestos-free packing. Its temperature limit with standard packing box construction is 450 F. If used to meet fugitive emissions, virgin PTFE should be alternated with carbon-filled PTFE or similar minimal cold-flowing material and live loaded.
  • Graphite laminated or preformed ring packing is chemically inert except when strong oxidizers are handled. This type of packing can be used for temperature applications approaching 2000 F. The biggest difficulty caused by this type of packing is very high packing friction, which often requires an oversized actuator. Performance is often compromised, because of significant increases in hysteresis and deadband.
  • Control valves should have no less than a Class II leakage rating. For most services, a Class IV rating is adequate. Class VI ratings should be considered only for applications requiring minimum possible leakage, and then only with owner approval.
  • Single-seated globe valves with metal-to-metal seating surfaces meet Class IV. Class V shutoff can be achieved by providing an improved plug to seat ring concentricity or lapping seating surfaces and/or increasing actuator thrust. Resilient seats on single-seated valves can provide Class VI shutoff.
  • Control valve flow characteristics are determined principally by the design of the valve trim. The three inherent characteristics available are quick opening, linear, and equal percentage. A modified equal percentage characteristics generally falling between linear and equal percentage characteristics is sometimes available.
  • Installed characteristics often differ significantly from inherent characteristics if the pressure drop across the control valve varies with the flow. As a result, equal percentage plugs are generally used for flow control applications because most of the system pressure drop is not across the control valve. Linear plugs are commonly used for applications where most of the system pressure drop occurs across the control valve.
  • As part of valve selection, the overall system in which the valve is to be installed should be considered. A typical system (in addition to the control valves) includes a pump or compressor, which provides energy, and other types of refinery equipment, such as piping, exchangers, furnaces, and hand valves, which offer resistance to flow. Note that the differential pressure between the pump head curve and the system pressure drop curve is the amount of pressure available for the control valve. If no control valve were used, the flow would always be at the rate indicated by the intersection of the two curves.

The primary factors that should be known for accurate sizing are:


(1) The upstream and downstream pressures at the flow rates being considered.


(2) The temperature of the fluid.


(3) The fluid phase (gas, liquid, slurry) and the density of the fluid (specific gravity, specific weight, molecular weight).


(4) The viscosity (liquids).


(5) The vapor pressure and critical pressure (liquids).


(6) Specific heat ratio (gas).


(7) The compressibility factor (gas).

Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution : A

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Electroma

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. ClO2