Venturi Flow Meter Working Principle Animation

 When a venturi flow meter is placed in a pipe carrying the fluid whose flow rate is to be measured, a pressure drop occurs between the entrance and throat of the venturi meter.

This pressure drop is measured using a differential pressure sensor and when calibrated this pressure drop becomes a measure of flow rate.

Venturi Flow Meter


Construction of Venturi meter
The following are the main parts and areas of venture meter:
The entry of the venture is cylindrical in shape to match the size of the pipe through which fluid flows. This enables the venture to be fitted to the pipe.

After the entry, there is a converging conical section with an included angle of 19’ to 23’.

Following the converging section, there is a cylindrical section with minimum area called as the throat.

After the throat, there is a diverging conical section with an included angle of 5’ to 15’.

Openings are provided at the entry and throat (at sections 1 and 2 in the diagram) of the venture meter for attaching a differential pressure sensor (u-tube manometer, differential pressure gauge, etc) as shown in diagram.

Operation of venturi meter:
The fluid whose flow rate is to be measured enters the entry section of the venturi meter with a pressure P1.

As the fluid from the entry section of venturi meter flows into the converging section, its pressure keeps on reducing and attains a minimum value P2 when it enters the throat. That is, in the throat, the fluid pressure P2 will be minimum.
The differential pressure sensor attached between the entry and throat section of the venturi meter records the pressure difference(P1-P2) which becomes an indication of the flow rate of the fluid through the pipe when calibrated.

The diverging section has been provided to enable the fluid to regain its pressure and hence its kinetic energy. Lesser the angle of the diverging section, greater is the recovery.

Applications of venturi meters

*It is used where high pressure recovery is required.
*Can be used for measuring flow rates of water,gases,suspended solids, slurries and dirty liquids.
*Can be used to measure high flow rates in pipes having diameters in a few meters.

Advantages of venturi meters
*Less changes of getting clogged with sediments
*Coefficient of discharge is high.
*Its behaviour can be predicted perfectly.
*Can be installed vertically, horizontally or inclinded.
*Low pressure drop (around 10% of Δp)
*Lower sensitivity to installation effects than orifice plates
*Less susceptibility to damage
*More suitable for gas flows with entrained liquid
*Comprehensive standards (ISO 5167)

Limitations of venturi meters
*They are large in size and hence where space is limited, they cannot be used.
*Expensive initial cost, installation and maintenance.
*Require long laying length. That is, the veturimeter has ti be proceeded by a straight *pipe which is free from fittings and misalignments to avoid turbulence in flow, for   satisfactory operation. Therefore, straightening vanes are a must.
*Low turndown (can be improved with dual range Δp cells)
*Greater cost to manufacture
*Greater susceptibility to “tapping errors” in high Reynolds number gas flows owing to the high velocity fluid passing the pressure tapping at the throat.
*Less experimental data than orifice plates




Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution : A

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Electroma

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. ClO2