Solenoid Valve Troubleshooting Practices

 Because there are so many potential reasons for solenoid valves to malfunction, they are often thought to be complex, trouble-prone devices. Actually, they are quite simple and very reliable.


Many of the problems originate outside the valves themselves, while others are caused by mis-application or improper installation. Troubleshooting should begin with a check of the voltage and pressure input.


The problem may be caused by an inoperative control relay or a fluctuating pressure regulator. If voltage and pressure are correct inspect the valve.


The main reasons a direct-acting solenoid valve fails to operate:

● Low or no voltage
● Burned-out solenoid
● Pressure higher than the valve’s rating
● Foreign matter in the valve
● Binding core or damaged core tube

To operate properly, a solenoid valve core must move within the core tube and contact the plugnut when the coil is energized.

You should hear a sharp metallic click at energization. Absence of the click usually indicates an electrical problem.

For most valves, voltage applied to the coil must be at least 85% of the nameplate voltage rating.

If the valve coil is receiving the proper voltage, absence of a click may mean that the line pressure is higher than the valve’s rating.

If line pressure is OK, foreign matter may be preventing the core from moving in the core tube. Core movement can also be restricted if the top of the core has been opened over millions of operations, if the disc is swollen or cut, or if the core itself has been damaged.

A pilot-operated valve might fail to operate when energized even though a click has been heard.

A no-flow condition may be caused by:
● Insufficient pressure drop across the valve
● Ruptured diaphragm or damaged pis- ton ring
● Plugged or restricted pilot orifice

Both pilot-operated and direct-acting valves can fail to operate when de-enerized because of:
● Faulty control circuit
● Scale or other foreign matter in the valve
● Binding core or damaged core tube
● Broken spring

Pilot-operated valves may also malfunction when de-energized due to:
● Plugged bleed orifice
● Damaged pilot seat or disc
● Damaged diaphragm or piston
● Insufficient pressure drop across the valve

Excessive solenoid noise (hum or chatter) can be caused by:
● Low voltage
● Faulty relay or improper electrical con- trol signal
● Loose solenoid parts
● Foreign matter on core or plugnut face
● Worn core of plugnut face
● Damaged spring
● Excessive system pressure

When troubleshooting 4-way valves con- trolling cylinders, it is important to follow the instructions provided with the valve. Some 4-way valves require an oil-mist lubricator for proper operation.

Pilot-activated 4-way valves normally require full- size piping for pressure inlet and exhaust. In some of these valves, restrictive speed control devices should be installed in the cylinder connections
Because faulty cylinder operation is often caused by the cylinder itself, it should be checked for:
● Misalignment between the piston rod and connected load
● Lack of lubrication
● Worn and leaking piston cups which allow fluid to exhaust through the valve
● Foreign matter in the speed controls
● System overloading, low line pressure, or undersized hoses or fittings

If the problems does not appear to be in the cylinder.

SOLENOID VALVE TROUBLESHOOTING GUIDE
MAINTENANCE PROCEDURES
Cleaning of filters and strainers should be part of your normal preventive maintenance program, along with cleaning and inspection of the valve. If the valve is not operating properly and corrective steps are required, confirm that the problem is in the valve and not caused by other conditions in the system.

Foreign matter in the valve, such as pipe joint sealant, corrosion from pipes and process vessels, mineral deposits and other solids, is a major cause of solenoid valve failure.If valve disassembly is required, always follow the instructions supplied with the valve for disassembly, cleaning and reassembly.

Before disassembling the valve, it is always best to have on hand those parts subject to wear which are most likely to require replacement.

Dirt on the valve body and on internal parts should be wiped off with a lint- free cloth.

On all valves, always be sure to reinstall the nameplate. The nameplate serves sometimes as a retainer to hold the solenoid to the valve.

MAINTENANCE TIPS
Direct-Acting Valves
Always turn off electrical and fluid sup- plies before disassembling a valve and loosen the solenoid base slowly to re- lease any trapped pressure.

Remove internal parts and wipe them clean with a lint-free cloth.

Examine the valve body for foreign mate- rials and deposits. Be especially careful not to scratch the valve seat or disc during cleaning. The movable core and core tube should be examined for signs of binding and wear. If present, all internal parts should be replaced.

The solenoid core must move freely in the core tube and should be free from signs of binding and excessive wear.

If there is excessive wear to the valve body (e.g. wire drawing of the seat), the valve should be replaced.

The disc at the end of the movable core or piston should be checked for signs of excessive impacting. If deep impressions are noted and the system involves liquids, a water hammer condition may exist. To protect the pipes and equipment in the system, install a water hammer cushion close to the valve inlet, or replace the valve.

After reassembly, check the valve operation by energizing the solenoid coil. A sharp metallic click should be heard if the valve is operating properly.

Pilot Operated Valves Cleaning and inspection procedures are essentially the same as for direct-acting valves. However, pilot operated valves also have a diaphragm or piston with bleed holes which must be cleaned. The piston should move freely in its cylinder and the piston rings should rotate freely in the groove.




Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Ferrules and Cross Ferruling

 Ferrules are identification labels provided for every wire terminations in an instrument, equipment, or electrical/instrumentation control panels. These tube-shaped sleeves can be inserted easily on each individual wire in a multi-core cable. In earlier days fixed digits/letters are used as ferrules, but now Instrumentation engineers/technicians prints out desired ferrules by using a ferrule printing machine. Typical Ferrule The numbers/ letters on the ferrules will be given as per the approved electrical hook up or loop diagrams. This helps technicians to easily identify a particular loop/wiring from a series of terminal blocks and to troubleshoot the desired terminal connection. Separate numbers on the ferrules distinguish the positive and negative polarities of wires, thus ensure the polarity protection of the instrument. Cross Ferruling  As a wire is connected on its both ends, it is quite useful to use a cross reference method for wire identification. Unlike normal ferru...