3 Port 2 Position Direct Acting Solenoid Valve Working Principle

 The valve is 3/2 Direct Acting pressure balance design i.e. area at the Seat (Part-19) and balancing Plunger O Ring (Part- 80) are same, thereby air force acting on the Plunger Seat is nullified which makes the valve to work merely on the spring force throughout its pressure range.

3 Port 2 Position Direct Acting Solenoid Valve

In the de-energised condition of the valve Port-1 is blocked and Port-3 is connection to Port-2. Port-4 is connected to spring chamber of the Actuator which is connected to Port-3 also.

On energizing the valve, Plunger (30) pulls up thereby connecting Port-1 and Port-2 and blocking Port-3. Port-4 remains connected to Exhaust Port-3. When the inlet is connected to Port-1, air passes through the small hole provided in the Plunger and acts on upper side of Plunger O Ring (80).

When the valve is energized, the Plunger (30) pulls up because of which the lower orifice opens up thereby connecting Port-1 to the outlet Port-3 and the upper orifice at Sleeve (Part-101) gets blocked.

In this condition force acting on the Plunger (30) due to seat at the Sleeve (Part-101) and on the Plunger (30) due to Plunger O Ring (80) are same because of their equal area.

When the valve is de-energised Port-2 gets connected to Port-3. However, as Port-3 has smaller opening as compared to its size, first air enters into the spring chambers through Port-4.


 Manual Override Operation : Push & Turn Type
When the solenoid is de-energised and inlet and outlet ports connected to the applying rated pressure, the valve can be operated either pressing the Manual Override, when the same is released, the valve returns back to the normal position.

The valve can also be locked in energized position by pushing the Manual Override and rotating clockwise. To avoid Manual Override returning back to normal condition, ensure that the same is turned above 90º.

The valve can be brought to normal condition by turning Manual Override anti clockwise.

Testing of the Valve at the Test Bench
Check at least once in 3 years or following your routine maintenance schedule.

a) Apply rated pressure at inlet port of the valve.

b) Plug outlet port.

c) Check operation of the valve and leakage at the exhaust ports and pilot vent at the rated and minimum working pressure by applying 75% to 120% rated voltage.

d) While keeping the solenoid de-energised, check operation and leakage from exhaust and pilot vent ports of the valve at the rated and minimum working pressure by operating Manual Override.

e) Without connecting air supply to the valve, operate Manual Override. Energise and De-energise Solenoid to check for the plunger movement (normally movement should not be there) which can be checked by click sound. After operating Manual Override if plunger movement is found, reduce length of the manual override by 0.3mm from its taper end. Continue this till click sound stops.

f) Check the insulation resistance of the Solenoid by applying 500V DC at terminals and the solenoid housing. It should be more than 100 Mega Ohms.

Source: Rotex


Comments

Popular posts from this blog

PLC Program for Mixing Tank

 Create a ladder diagram for controlling a batch mixing process. Implement a PLC program for mixing tank or Mixing Process using PLC Ladder Logic. PLC Program for Mixing Tank Fig : Mixing tank A tank is used to mix two liquids. The required control circuit operates as follows: A. When the START button is pressed, solenoids A and B energize. This permits the two liquids to begin filling the tank. B. When the tank is filled, the float switch trips. This de-energizes solenoids A and B and starts the motor used to mix the liquids together. C. The motor is permitted to run for 1 minute. After 1 minute has elapsed, the motor turns off and solenoid C energizes to drain the tank. D. When the tank is empty, the float switch de- energizes solenoid C. E. A STOP button can be used to stop the process at any point. F. If the motor becomes overloaded, the action of the entire circuit will stop. G. Once the circuit has been energized, it will continue to operate until it is manually stopped. Solution...

What is Relay? How it Works? Types, Applications, Testing

 We use relays for a wide range of applications such as home automation, cars and bikes (automobiles), industrial applications, DIY Projects, test and measurement equipment, and many more. But what is Relay? How a Relay Works? What are the Applications of Relays? Let us explore more about relays in this guide. What is a Relay? A Relay is a simple electromechanical switch. While we use normal switches to close or open a circuit manually, a Relay is also a switch that connects or disconnects two circuits. But instead of a manual operation, a relay uses an electrical signal to control an electromagnet, which in turn connects or disconnects another circuit. Relays can be of different types like electromechanical, solid state. Electromechanical relays are frequently used. Let us see the internal parts of this relay before knowing about it working. Although many different types of relay were present, their working is same. Every electromechanical relay consists of an consists of an Elect...

Chlorine dioxide Analyzer Principle

 Chlorine dioxide measurement Chlorine dioxide (ClO2) is an instable, non-storable, toxic gas with a characteristic scent. The molecule consists of one chlorine atom and two oxygen atoms – represented in the chemical formula ClO2. It is very reactive. To avoid the risk of spontaneous explosions of gaseous chlorine dioxide or concentrated solutions, it is generally handled in dilution with low concentrations. ClO2 is soluble in water, but tends to evaporate quickly. Typically it is prepared on site, for example from hydrochloric acid and sodium chlorite. The procedure provides solutions with approx. 2 g/l ClO2 that can be safely handled and stored for several days. Image Credits : krohne Sensor Parts : Reference electrode Applied chlorine dioxide specific potential Current needed to maintain the constant potential Counter electrode Measuring electrode The disinfection effect of ClO2 is due to the transfer of oxygen instead of chlorine, so that no chlorinated byproducts are formed. C...